3/31/2024 0 Comments Gx works 2 upgrade![]() This was introduced in a fairly recent version of GX Works2 and is only possible on FX because only FX has the "one program file" limit in the CPU. In that case, the compiler will join these POU's into one MAIN program file before downloading it into the cpu. In that case, Mitsubishi introduced something called "program linkage order setting" which allows you to join a number of simple ladder POU's (up to 256 i think). It has to be noted that Mitsubishi introduced a solution to this problem which allows multiple simple ladder POU's inside one MAIN program file IF you upgrade your project from simple ladder to simple ladder with labels (and therefor introduce a compiler stage). GX Works2 has improved functionality and operability, with easier-to-use features compared to ex-isting GX Developer. Upgrading to structured program will not help if you want your POU to remain in simple ladder (and not structured ladder) since it will have the same limitation. Getting to Know GX Works2 Main functions of GX Works2 GX Works2 2 - 1 2 Getting to Know GX Works2 GX Works2 is a programming tool for designing, debugging, and maintaining programs on Win-dows®. I don't understand how you managed to import an FX3U program from GX Developer into GX Works2 which has more than one POU (Abart, ERRORS_G.)? In simple ladder (GX developer), an FX3U program can only have one POU called MAIN because there can only be one "program file" in the CPU called MAIN.